Title: Three-dimensional air distribution analysis of different outflow typed operating rooms at different inlet velocities and room temperatures
Authors: Uludağ Üniversitesi/Mühendislik Fakültesi/Makine Mühendisliği Bölümü.
Ufat, Hande
Kaynaklı, Ömer
Yamankaradeniz, Nurettin
Yamankaradeniz, Recep
AAA-1753-2021
AAK-4166-2021
57195235906
8387145900
26645227400
6507733785
Keywords: Thermodynamics
Engineering
Operating room air conditioning
Computational fluid dynamics
Air distribution
Laminar air flow unit
Validation
Numerical simulation
Ventilation performance
Thermal comfort
Indoor environment
Airborne infection
Flow unit
Theater
System
Contamination
Quality
Jet
Issue Date: 6-Apr-2017
Publisher: Sage Puplications
Citation: Ufat, H. vd. (2017). ''Three-dimensional air distribution analysis of different outflow typed operating rooms at different inlet velocities and room temperatures''. Advances in Mechanical Engineering, 9(7), 1-12.
Abstract: It is important to provide a regular unidirectional air distribution in an operating room to reduce the number of particles. Measurements were taken in the one of the operating rooms at Uludag University Medical School, with laminar air flow unit and two-cornered outlet which was thought to have some airflow problems. Moreover, a three-dimensional computational fluid dynamics model has been developed where the measurements were taken in. The distributions of air velocity, temperature, and relative humidity have been examined and compared with the measurements to validate the computational fluid dynamics analyses. In addition to present model, four-cornered outlet operating room has been analyzed and compared with the results of two-cornered one. It is concluded that the case of four-cornered outlet provides more suitable thermal distribution, which results in a reduction of the particle numbers in the interior. Although there is no significant change in temperature and relative humidity in the operating room, air distribution changes dramatically.
URI: https://doi.org/10.1177/1687814017707414
https://journals.sagepub.com/doi/10.1177/1687814017707414
http://hdl.handle.net/11452/30778
ISSN: 1687-8140
Appears in Collections:Scopus
Web of Science

Files in This Item:
File Description SizeFormat 
Ufat_vd_2017.pdf6.84 MBAdobe PDFThumbnail
View/Open


This item is licensed under a Creative Commons License Creative Commons