Bu öğeden alıntı yapmak, öğeye bağlanmak için bu tanımlayıcıyı kullanınız:
http://hdl.handle.net/11452/30778
Başlık: | Three-dimensional air distribution analysis of different outflow typed operating rooms at different inlet velocities and room temperatures |
Yazarlar: | Uludağ Üniversitesi/Mühendislik Fakültesi/Makine Mühendisliği Bölümü. Ufat, Hande Kaynaklı, Ömer Yamankaradeniz, Nurettin Yamankaradeniz, Recep AAA-1753-2021 AAK-4166-2021 57195235906 8387145900 26645227400 6507733785 |
Anahtar kelimeler: | Thermodynamics Engineering Operating room air conditioning Computational fluid dynamics Air distribution Laminar air flow unit Validation Numerical simulation Ventilation performance Thermal comfort Indoor environment Airborne infection Flow unit Theater System Contamination Quality Jet |
Yayın Tarihi: | 6-Nis-2017 |
Yayıncı: | Sage Puplications |
Atıf: | Ufat, H. vd. (2017). ''Three-dimensional air distribution analysis of different outflow typed operating rooms at different inlet velocities and room temperatures''. Advances in Mechanical Engineering, 9(7), 1-12. |
Özet: | It is important to provide a regular unidirectional air distribution in an operating room to reduce the number of particles. Measurements were taken in the one of the operating rooms at Uludag University Medical School, with laminar air flow unit and two-cornered outlet which was thought to have some airflow problems. Moreover, a three-dimensional computational fluid dynamics model has been developed where the measurements were taken in. The distributions of air velocity, temperature, and relative humidity have been examined and compared with the measurements to validate the computational fluid dynamics analyses. In addition to present model, four-cornered outlet operating room has been analyzed and compared with the results of two-cornered one. It is concluded that the case of four-cornered outlet provides more suitable thermal distribution, which results in a reduction of the particle numbers in the interior. Although there is no significant change in temperature and relative humidity in the operating room, air distribution changes dramatically. |
URI: | https://doi.org/10.1177/1687814017707414 https://journals.sagepub.com/doi/10.1177/1687814017707414 http://hdl.handle.net/11452/30778 |
ISSN: | 1687-8140 |
Koleksiyonlarda Görünür: | Scopus Web of Science |
Bu öğenin dosyaları:
Dosya | Açıklama | Boyut | Biçim | |
---|---|---|---|---|
Ufat_vd_2017.pdf | 6.84 MB | Adobe PDF | Göster/Aç |
Bu öğe kapsamında lisanslı Creative Commons License