Bu öğeden alıntı yapmak, öğeye bağlanmak için bu tanımlayıcıyı kullanınız:
http://hdl.handle.net/11452/34761
Başlık: | Investigation of the number of particles in an operating room at different ambient temperatures and inlet velocities |
Yazarlar: | Uludağ Üniversitesi/Mühendislik Mimarlık Fakültesi/Makine Mühendisliği Bölümü. Ufat, Hande Kaynaklı, Ömer Yamankaradeniz, Nurettin Yamankaradeniz, Recep AAA-1753-2021 AAK-4166-2021 8387145900 57195235906 26645227400 6507733785 |
Anahtar kelimeler: | Construction & building technology Energy & fuels Indoor air quality Operating room air conditioning Particle counting Operating room Laminar air-flow Ventilation performance Indoor environment Airborne infection Thermal comfort Quality Theater Contamination System Staff Air conditioning Air quality Computational fluid dynamics Indoor air pollution Operating rooms Surgery Temperature Air velocities Computational fluid dynamics analysis Field measurement Indoor air quality Low temperatures Operating condition Particle counting Particle counts Air |
Yayın Tarihi: | 11-Eki-2017 |
Yayıncı: | Taylor & Francis |
Atıf: | Ufat, H. vd. (2018). ''Investigation of the number of particles in an operating room at different ambient temperatures and inlet velocities''. International Journal of Ventilation, 17(3), 209-223. |
Özet: | This study presents some field measurements in an operating room of air velocity, ambient temperature and particle counts on the operating table. Moreover, computational fluid Dynamics analyses of the operating room were performed and compared with the measurements. Measurements were taken under the preferred operating conditions by surgical staff (at 19 degrees C) and then at different ambient temperatures (from 20 to 22 degrees C, varying by one-degree increments) and average inlet air velocities (V-j) (0.1 and 0.2 m/s). The preferred one by surgical staff is 0.1 m/s and the maximum that can be reached is 0.2 m/s, with the current system. The results show that the particle count decreased at V-j of 0.2 m/s and low temperatures. |
URI: | https://doi.org/10.1080/14733315.2017.1392107 https://www.tandfonline.com/doi/full/10.1080/14733315.2017.1392107 http://hdl.handle.net/11452/34761 |
ISSN: | 1473-3315 2044-4044 |
Koleksiyonlarda Görünür: | Scopus Web of Science |
Bu öğenin dosyaları:
Bu öğeyle ilişkili dosya bulunmamaktadır.
DSpace'deki bütün öğeler, aksi belirtilmedikçe, tüm hakları saklı tutulmak şartıyla telif hakkı ile korunmaktadır.